D1点短路时的情况:
等效电阻: = + +
=0.36-0.0025+0.060835
=0.418335
短路电流的周期分量的标幺值为:
= / + /
=1/0.418335+1/0.015
=69.0571
D1点是电流基准值为: =100/( )kA=0.251kA
短路电流的周期分量的有名值为: 0.251kA=17.3333kA
冲击电流的有名值为: = 0.251=44.1235kA
短路电流的全电流有效值为: = 0.251kA=26.1727kA
短路容量: = =6905.71MVA
D2点短路时的情况:
等效电阻: = + +
=0.015+0.060835-0.0025=0.073335
短路电流的周期分量的标幺值为:
= / + / =1/0.073335+1/0.36=16.4138
D2点是电流基准值为: =100/( )kA=0.502kA
短路电流的周期分量的有名值为: 0.502kA=8.2397kA
冲击电流的有名值为: = 0.502=20.9749kA
短路电流的全电流有效值为: = 0.502kA=12.4417kA
短路容量: = =1641.38MVA
D3点短路时的情况:
等效电阻: = + ( + ) ( + ) / ( + + + )
=0.03335+(0.36-0.0025)(0.015+0.060835)/(0.36-0.0025+0.015+0.060835)
=0.09591
= ( * ( + ) + * ( + )) / ( + + + )
=(1 ( + ) + 1 ( + )) / ( + + + )
=1
短路电流的周期分量的标幺值为:
= / X23=1/0.09591=10. 4264
D3点是电流基准值为: =100/( )kA=5.4986kA
短路电流的原文请找腾讯752018766辣.文-论'文.网
http://www.751com.cn 周期分量的有名值为: 5.4986kA=57.3308kA
冲击电流的有名值为: = 5.4986=145.9405kA
短路电流的全电流有效值为: = 5.4986kA=86.5677kA
短路容量: = =1042.64MVA
短路计算总结:
表3-1
短路点的编号 基准容量 (MVA)
基准电压VaV(kV) 稳态短路电流标么值 稳态短路电流有名值(kA) 短路电流冲击值 (kA)
短路全电流最大有效值 (kA)
短路容量 ( MVA)d1
100 230 69.0571 17.3333 44.1235 26.1727 69.0571d2
115 16.4138 8.2397 20.9749 12.4417 1641.38d3
10.5 10.4264 57.3308 145.9405 86.5677 1042.64
第四章 主要电气设备的选择和校验
4.1 断路器的选择
断路器型式的选择:除需满足各项技术条件和环境条件外,还考虑便于安装调试和运行文护,并经技术经济比较后才能确定。根据我国当前制造情况,电压6-220kV的电网一般选用少油断路器,电压110-330kV电网,可选用 或空气断路器,大容量机组釆用封闭母线时,如果需要装设断路器,宜选用发电机专用断路器。
断路器选择的具体技术条件如下:
(1)电压: ≤ ---电网工作电压, ---断路器的额定电压
(2)电流: ≤ ---最大持续工作电流, ---断路器的额定电压
(3)开断电流: ≤
---断路器实际开断时间t秒的短路电流周期分量; ---断路器额定开断电流
(4)动稳定: ≤
---断路器极限通过电流峰值; ---三相短路电流冲击值
(5)热稳定:
--- 短路电流的热效应或热脉冲; --- 断路器t秒热稳定电流