菜单
  

    to the return grille, and recommended that the return be placed close to pollutant sources and
    away from occupied workstations.
    We did not find any studies that examined the influence of workstation characteristics on
    the performance of floor-mounted mixing systems. It is possible that effective mixing could be
    inhibited by workstation partitions, particularly for those workstations not located above a
    diffuser. This hypothesis, however, has not been empirically studied.
    Overall, empirical evidence suggests that mixing air distribution systems are capable of
    producing a relatively uniform indoor environment in office settings, including open-plan offices.
    In addition, when used appropriately mixing systems can achieve acceptable levels of ventilation
    efficiency, pollutant removal efficiency and thermal conditions.
    IRC-RR-161 7 Office Air Distribution Systems and Environmental Satisfaction
    2.2 Displacement Systems and Physical Conditions
    A number of studies have examined the IAQ and thermal conditions arising from
    displacement air distribution systems in office settings (e.g. Akimoto, Nobe, Tanabe, & Kimura,
    1996; Gan, 1995; Jiang et al., 1992; Nielsen, 1996; Olesen, Koganei, Holbrook, Seelen, &
    Woods, 1994; Tanabe & Kimura, 1996; Xing, Hatton, & Awbi, 2001).
    Empirical evidence indicates that displacement systems produce two horizontal zones
    within office spaces. The lower zone exhibits an upward convective flow, with air temperature,
    pollutant concentration and age of air all increasing with height from the floor. In the upper zone,
    these displacement characteristics are less pronounced, and the airflow pattern tends towards
    mixed air and more uniform conditions. The height of the lower zone is primarily dependent on
    the supply airflow rate, the amount and distribution of heat sources within the space, and the
    thermal plumes created by these heat sources (ASHRAE, 2001; Yuan et al., 1998). Studies
    reviewed by Yuan et al. (1998) have also suggested that displacement airflow patterns are
    influenced by factors such as the temperature of external walls and windows, the difference
    between supply and room temperature, and the ceiling height.
    Research suggests that, under certain conditions, displacement systems can achieve better
    IAQ and contaminant removal efficiency in the occupied zone, as compared to ceiling-mounted
    mixing systems. The main determinant of this improved performance is the transition between
    the lower and upper zones. Improvements in IAQ are typically reported when the occupant’s
    breathing zone falls within the lower zone. However, if there are substantial pollutant sources
    located close to floor level, or if thermal plumes are not sufficient to remove pollutants to the
    upper zone, these improvements can be undermined. In such cases, pollutants will remain in the
    lower zone and can result in reduced IAQ in the occupant’s breathing zone.
    One drawback of increasing the height of the lower zone is that it can lead to
    uncomfortable vertical temperature differences. As the lower zone is characterised by an upward
    flow, the difference in temperature between the occupant’s head and ankles could exceed that
    required for local thermal comfort2
    . Therefore, the operation of displacement systems requires a
    careful balance between promoting IAQ, whilst restricting vertical temperature differences. The
    use of chilled ceiling panels has been suggested to reduce the vertical temperature gradient, and
    so provide a wider range of conditions in which both IAQ and thermal requirements can be
    achieved (Novoselac & Srebic, 2002).
    A final consideration of displacement systems is their potential for creating draughts. As
    air is supplied at floor level, and at cooler temperatures than typically used in mixing systems,
  1. 上一篇:数控系统在平面磨床上应用英文文献和中文翻译
  2. 下一篇:组合夹具系统的设计英文文献和中文翻译
  1. 中央空调系统英文文献和中文翻译

  2. 船舶空气调节系统空调英文文献和中文翻译

  3. 通风空调(暖通空调)风...

  4. 利用地板下的空气提高建...

  5. 在恒载作用下破坏时的再...

  6. 建筑暖通空调系统英文文献和中文翻译

  7. 采暖空调英文文献和中文翻译

  8. 乳业同业并购式全产业链...

  9. 当代大学生慈善意识研究+文献综述

  10. java+mysql车辆管理系统的设计+源代码

  11. 杂拟谷盗体内共生菌沃尔...

  12. 大众媒体对公共政策制定的影响

  13. 中考体育项目与体育教学合理结合的研究

  14. 电站锅炉暖风器设计任务书

  15. 十二层带中心支撑钢结构...

  16. 酸性水汽提装置总汽提塔设计+CAD图纸

  17. 河岸冲刷和泥沙淤积的监测国内外研究现状

  

About

751论文网手机版...

主页:http://www.751com.cn

关闭返回