摘要:随着非线性电力电子器件的大量使用,给电网中注入了大量的谐波,对用电设备造成了严重的危害,治理谐波刻不容缓。混合型有源电力滤波器是有效治理谐波的装置,其控制策略是混合型有源电力滤波器的核心环节之一,对它进行研究有重要的现实意义。53782
本文以混合型电力滤波器的控制策略为研究对象。重点研究了双闭环控制方法,即电流内环控制和电压外环控制,其中电流内环控制采用了滞环比较控制策略,电压外环控制采用了PI控制策略。
毕业论文关键词:混合型有源电力滤波器,控制策略,双闭环控制
Abstract:With the extensive use of non-linear power electronic devices, the grid is injected a large number of harmonics and serious harm is caused on the electrical equipments, so governance harmonic delay is needed.Hybrid active power filter is effective governance harmonic device, its control strategy is one of the core areas of hybrid active power filter, its study has important practical significance.
In this paper, it takes the control strategy of hybrid power filter as the subject . Focus on the double-loop control method, the outer voltage control and current loop control, which is controlled by the inner current loop hysteresis control strategy, and voltage loop control using a PI control strategy.
Keywords: Hybrid active power filter, Control strategy, Double closed loop control
目 录
1 绪论 5
1.1 课题背景 5
1.2 谐波的产生及危害 5
1.3 谐波的治理 6
1.4 本文主要研究内容 6
2 无源滤波器与有源电力滤波器论述 7
2.1 无源滤波器 7
2.2 有源电力滤波器 8
2.3 混合型有源电力滤波器 10
3 混合型有源电力滤波器控制策略的研究 15
3.1 电流控制方法 16
3.2 直流侧电压PI控制 19
3.3 本章小结 21
结论 22
参考文献 23
致谢 24
1 绪论
1.1 课题背景
随着现代工业技术的飞跃发展,电气化设备已经深入到每个人的生活当中,随之带来的是电力系统中的电力负荷结构发生了极大的变化,一些非线性负荷如半导体整流器、变频器、电气化铁路的发展给电网注入了大量的谐波,严重影响了公用电网的电能质量。电网中大量的谐波污染严重影响着用电设备的安全,也降低了人们的生活质量。谐波治理问题已经引起了各国的极大关注,因此必须采取一定的措施来抑制谐波,保证公用电网的电能质量。
混合型有源电力滤波器在电网谐波的治理与无功补偿中发挥了不可估量的作用。
1.2 谐波的产生及危害
随着电力电子技术的快速发展,各种电力电子器件被大量的使用。比如利用晶闸管整流和利用变频器进行调速的设备给电力系统中注入大量的谐波电流,使得电网发生畸变,随之而来的便是电网污染,造成电力系统中很多设备的安全正常运行。
谐波的产生:产生谐波的根本原因是当负载有电流流过时,其电流与所加的电压不是线性关系,从而形成了非正弦电流,即谐波电流。电网中的许多电力电子设备、变压器、发电机、电弧炉和荧光灯等都是谐波源。在电力电子器件大规模使用前,电力系统自身也包含大量的产生谐波的非线性元器件,电力电子器件大规模使用后,电力电子装置成为主要的谐波源。