摘要本毕业设计主要是进行对苏州某办公楼的暖通空调系统设计,该办公楼地上五层,无地下室,通过对工程的经济性及可行性进行分析,确定了该工程采用风冷热泵作为冷热源,并依此进行了详细的设计计算等诸多内容。本设计主要的计算内容包括建筑的冬夏季符合计算、系统方案的确定、设备选型计算、水力计算、风路风压计算等。经过分析计算,决定了该工程采用“空气——水”系统及“全空气”系统相结合;考虑苏州当地的气候及建筑物的条件,充分考虑其经济性及节能环保等方面,在屋顶放置风冷热泵作为冷热源,并说明该工程设计的可行性。最后对设计的内容进行分析总结,并分析设计中应注意的主要内容。30223
关键词 空调系统 空气——水 全空气系统
毕业论文设计说明书外文摘要
Title An office building in Suzhou HVAC engineering design
Abstract
The graduation project is mainly for HVAC system design for an office building in Suzhou, the five-story building on the ground, without the basement, through the analysis of the economic feasibility of the project and determine the project as a cold air-cooled heat pumps heat, and so were a lot of calculation and detailed design. These design calculations include winter and summer construction compliance calculations to determine system solutions, equipment selection calculations, hydraulic calculations, the air duct pressure calculation. After analysis and calculation to determine the project uses the "air - water" systems and "full air" systems integration; considerate the local climate conditions of Suzhou and the building, give full consideration to its economy and energy-saving and environmental protection, placed on the roof air-cooled heat pump as a heat source, and demonstrate the feasibility of the project design. Finally, the design of the content analysis are summarized and analyzed the design should pay attention to the main content.
Keywords Air Conditioning System air – water full air
目 次
1 引言 1
1.1 系统的介绍 1
1.2 建筑物概况 1
1.3 设计内容 1
2 设计参数及依据 3
2.1 地理气象参数 3
2.2 建筑围护结构参数 3
2.3 室内设计参数 3
2.4 设计规范及标准 4
3 空调负荷计算 5
3.1 夏季冷负荷计算 5
3.2 冬季热负荷计算 8
4 办公室空调负荷计算 10
4.1 外墙冷负荷计算 10
4.2 外窗冷负荷计算 11
4.3 日射得热冷负荷 12
4.4 设备散热冷负荷 13
4.5 照明散热冷负荷 13
4.6 人体散热冷负荷 14
4.7 新风负荷 14
4.8 该办公室逐时冷负荷汇总(不包括新风负荷) 14
4.9 各个房间冷负荷汇总 15
4.10 围护结构耗热量 18
4.11 冷风渗透耗热量 18
4.12 冬季负荷计算汇总 18
5 空调系统的选择 22 苏州某办公楼暖通空调工程设计:http://www.751com.cn/gongcheng/lunwen_25839.html