K 0.90
A 21.28
Qc 146.01 137.19 131.90 128.37 128.37 131.90 138.95 147.78 156.60 165.42 172.48
表2.6 屋面一瞬时传热冷负荷
时间 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00
tc 34.1 33.1 32.7 33.0 34.0 35.8 38.1 40.70 43.50 46.10 48.30
td 0.10
kα 0.98
kρ 0.94
tc'(τ) 31.51 30.58 30.22 30.49 31.41 33.07 35.19 37.58 40.16 42.56 44.59
tR 26.00
Δt 5.51 4.58 4.22 4.49 5.41 7.07 9.19 11.58 14.16 16.56 18.59
K 3.08
A 333.67
Qc 5657.55 4710.83 4332.14 4616.16 5562.88 7266.97 9444.43 11905.91 14556.72 17018.20 19100.98
表2.7 屋面四瞬时传热冷负荷
时间 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00
tc 34.1 33.1 32.7 33.0 34.0 35.8 38.1 40.70 43.50 46.10 48.30
td 0.10
kα 0.98
kρ 0.94
tc'(τ) 31.51 30.58 30.22 30.49 31.41 33.07 35.19 37.58 40.16 42.56 44.59
tR 26.00
Δt 5.51 4.58 4.22 4.49 5.41 7.07 9.19 11.58 14.16 16.56 18.59
K 0.55
A 160.00
Qc 484.44 403.38 370.95 395.27 476.34 622.26 808.71 1019.48 1246.46 1457.23 1635.58
表2.8 人员散热引起的冷负荷
时间 8:00 9:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00
CLQ 0.55 0.64 0.70 0.75 0.79 0.81 0.84 0.86 0.88 0.89 0.91 苏州市某办公楼空调工程设计(7):http://www.751com.cn/gongcheng/lunwen_8113.html