摘要: 本设计为北京独栋别墅地源热泵中央空调系统。与传统空调相比,在节能方面有很大的优势。本设计内容包括: 空调冷负荷的计算;空调系统的划分与系统方案的确定;空调末端处理设备的选型;风系统的设计与计算;室内送风方式与气流组织形式的选定;水系统的设计、布置与水力计算;地埋管换热器的选型;风管系统与水管系统保温层的设计;消声防振设计等内容。在节能和室内舒适度的要求下,采取风机盘管加新风系统这套方案。27787
毕业论文关键词: 别墅;土壤源热泵;中央空调;风机盘管;地埋管换热器
Design of Villa Ground Source Heat Pump Central Air-conditioning System in Beijing
Abstract: The design for the Beijing villa ground source heat pump central air-conditioning system.Compared with the traditional air conditioning, has great advantages in energy saving.The design includes: cooling load calculation; determine the air conditioning system design and system; air terminal handling equipment selection; the wind system design and calculation; selection of indoor air and airflow form; design calculation, water systemlayout and hydraulic pipe; heat exchanger; the wind pipe layer design of insulationsystem and plumbing systems; muffler vibration design etc..In energy saving and indoor comfort requirements, take a fresh air fan coil system.
Keywords: Villa, Soil source heat pump, Central air conditioning, Fan coil, Heat exchanger
目录
1 绪论 1
1.1 课题背景和意义 1
1.2 国内外研究现状与水平 1
1.3 发展趋势 3
1.4 地源热泵的特点 4
2 工程概况与设计依据 6
2.1 建筑平面图和剖面图 6
2.2 国家主要规范和行业标准 6
2.3 工程概况 6
2.4 气象参数和地址参数 6
2.5 地源热泵简介 7
2.6 初步方案 7
3 负荷计算 9
3.1 夏季空调冷负荷计算 9
3.1.1 围护结构冷负荷 9
3.1.2 室内热源散热形成的冷负荷 11
3.2 冬季热负荷的计算 12
3.2.1 围护结构基本耗热量 12
3.2.2 围护结构的修正耗热量 13
3.3 湿负荷计算 14
3.4 负荷计算数据汇总 14
4 新风负荷计算 16
4.1 新风量的确定 16
4.2 夏季新风冷负荷计算 16
4.3 新风量汇总及新风负荷 16
5 空气处理设备的选型 18
5.1 风机盘管的选型 18
5.1.1 送风量的计算 18
5.1.2 风机盘管的选取 19
5.2 新风机组的选择 20
5.2.1 新风机组的计算 20
5.2.2 新风机组的型号及布置 20
5.3 气流组织计算 21
5.4 风口选取 22
6 风系统的水力计算 23
6.1 计算依据 23
6.2 水力计算 23
7 空调水系统水力计算 27
7.1 水力计算 27
7.2 冷凝水管道设计 33
7.2.1 排放的施工要求 33
7.2.2 管径确定 33
7.2.3 管道保温 34
8 空调冷热源选择 35
8.1 地源热泵机组 35
8.2 地下换热器尺寸的确定及布置 36 北京某独栋别墅地源热泵中央空调系统设计+CAD图纸:http://www.751com.cn/gongcheng/lunwen_22397.html