摘要: 本文针对400V低压配电网络负荷的不平衡,冲击负荷造成无功补偿设备的投切振荡,大负荷用户,不能充分利用补偿设备,传统补偿方法缺陷较多,功率因数较低,仍需从系统汲取大量无功功率的特点,提出一种分相投切电容器的方法来补偿无功功率的方法,既解决了投切振荡的问题,又在最大程度上利用电容器,使得无功功率尽可能的就地平衡。65427
关键词:配电网, 无功补偿, 分相补偿, 并联电容器, 低电压
Abstract: For 400V low voltage distribution network load imbalance, the impact load of reactive power compensation equipment for oscillation, large load of users, can not make full use of the compensation device, the traditional compensation method flaw, the power factor is low, still need to learn a lot from the system reactive power characteristic, put forward a method of congenial points cut capacitor to compensate reactive power, the method of both solved the problem of the cutting vibration, and the maximum use of capacitor, makes the balance of reactive power as much as possible.
Keywords: Distribution network, reactive power compensation, phase compensation, shunt capacitor, low voltage
目录
1 绪论 4
1.1 研究背景 5
1.2 无功补偿的意义 5
1.3 无功补偿装置的现状 6
1.4 本文的主要工作 8
2. 配电网无功补偿的理论基础 8
2.1 无功补偿的基本原理 8
2.2 无功补偿的合理配置原则 8
2.3 无功补偿的作用 9
2.4 无功补偿提高功率因数的概念 9
2.5 并联补偿电容器容量计算 11
3. 低压配电网的补偿策略 13
3.1 低压配电网无功补偿的方法 13
3.2 三种无功补偿方法的优缺点 14
3.3 低压配电网并联电容器的投切策略 14
4. 算例 17
总结展望 20
参考文献 21
致谢 22
1 绪论
随着社会的发展,我国工农业对用电的质量和需求量越来越大,然而配电网在传输电能时会有大量的无功功率,这大大减低了电能的质量。大量的无功负荷若是得不到补偿,不仅不降低功率因数,同时造成电能质量的下降。因此对中低压配电网进行无功补偿意义重大。
在我国电力工业迅猛发展的今天, 对电网的无功补偿与电压支撑已成为电网安全稳定运行的决定性因素。电力系统配电网无功补偿的主要目的是为了提高配电系统的功率因数和供电质量、减小线路损耗等。
用电设备采用无功补偿可以提高电网电压,减少无功损耗,提高输电能力,能够杜绝输电线路电线过热以及开关过流跳闸等事故,它能够保障供电安且全节能高效。[1]
不同于欧美发达国家,我国的一些电网设施还不完善,电力传输技术还有缺陷,因此,操作简单,经济方便的无功补偿方法便成了我国提高电网功率因数的首选。 尽管如此, 我国在无功补偿方面的研究仍是有着大量的工作要做。特别是对中低压配电网的无功补偿的加强及对其配置方面的优化和无功平衡,对于提高功率因数,减少电网损耗,保证电压质量,提高设备的利用率有着重要的作用和意义。[2]