     RoomIndoor temperature(℃) 

    Indoor relative humidity (%) Fresh air volume

    (m3/h.p)

     summer winter summer winter

    Hotel room 25 20 60±5 —— 30

    Conference room 25 18 60±5 —— 30

    Open office area 26 18 60±5 —— 30

    Private room of catering 25 18 55±5 —— 30

    Dining room 23 18 55±5 —— 20

    Determining air conditioning system Determining wind system of air conditioning

    By comparison and selection of air-conditioning systems, the design uses three kinds of air conditioning systems in the form, in particular: dining hall, open office area using primary return air system; fan-coil units with fresh air system is adopted for the guest rooms of the hotel and private dining rooms; large conference rooms using varied refrigerant volume air conditioning system (VRV).

    Primary return air system is adopted for the dinning room and open office area. This air conditioning system supplies large amount of air and reduce the indoor air pollution. The air handling equipments are centralized in the engine room so that’s convenient to be managed and maintained. Fresh air can be adjusted by season and achieve annual energy saving operation by multi-state regulation. Meanwhile achieve economic effect

    Fan-coil units with fresh air system is adopted for the guest rooms of the hotel and private dining rooms. According to investigation, private dinning rooms and guest rooms are used at different times and the load of different rooms are mutative and inconsist. That requires separate control. The fan-coil units with fresh air system can control the temperature of different room inpidually and the air conditioning systems for different rooms operating independently of each other.

    VRV system is used for the large conference room. The system can be started or stopped at any time based on the operation situation of each room. What’s more is we can achieve heating in winter. Due to the large amount of air to exhaust of the large conference room and private rooms and the temperature difference between fresh air and exhausted air, we use full-heat type fresh air exchanger to process the fresh air. By this method, we not only make use of the exhaust energy but also reduce the fresh air units. The refrigeration capacity of the host and the energy consumption of chilled water transportation achieve corresponding reduction.

     Determining water system of air conditioning

    The direct return system is adopted for the 1st and 2nd floor of the dinning room and other area using the indirect return system. In consideration of the great resistance of the long pipeline for the private rooms and guest rooms, coupled with the great resistance losses of the fan-coil units, usually in 30-50kPa, the direct return system can not achieve hydraulic balance. So indirect return system is applied in these rooms. The scale of the water system for 1st and 2nd floor is not large and the hydraulic stability is well, so the direct return system is a proper application. Direct return system can also reduce initial investment.

  1. 上一篇:镁合金板材弯曲工艺冷冲压英文文献和中文翻译
  2. 下一篇:模具设计的知识库系统英文文献和中文翻译
  1. 汽车乘员舱的声振耦合英文文献和中文翻译

  2. 立体光照成型的注塑模具...

  3. 数控机床英文文献和中文翻译

  4. 工业机械手英文文献和中文翻译

  5. 低频振动的铁路车轴的状...

  6. 接头的形状对沥青塞接头...

  7. 数控加工技术英文文献和中文翻译

  8. 大众媒体对公共政策制定的影响

  9. java+mysql车辆管理系统的设计+源代码

  10. 酸性水汽提装置总汽提塔设计+CAD图纸

  11. 中考体育项目与体育教学合理结合的研究

  12. 乳业同业并购式全产业链...

  13. 当代大学生慈善意识研究+文献综述

  14. 杂拟谷盗体内共生菌沃尔...

  15. 十二层带中心支撑钢结构...

  16. 电站锅炉暖风器设计任务书

  17. 河岸冲刷和泥沙淤积的监测国内外研究现状

  

About

751论文网手机版...

主页:http://www.751com.cn

关闭返回